19'' 6U Chassis page 11/71
Figure 10: Ground screw location.
Connect the cable(s) provided to a correctly protected -48V supply.
Fuse Rating: 2.5A, as follows:
Blue - 0V Battery
Brown - -48V
Connect the other end to the power unit on the front panel of the
MS430502M chassis.
During the powering up sequence the HW led on the front panel of the MS430502M
chassis will momentarily flash green before remaining on. One or two seconds later the
SW led on the front panel will come on indicating the correct loading of the software.
With normal led activity i.e. all leds on and green, the MS430502M chassis is ready for
setting up. If this is not the case consult the relevant section of the Maintenance
Manual.
End procedure
System and Module Set-Up
Management of the MS430502M chassis can be achieved in a number of ways:
Locally and remotely:
The on-board SNMP agent allows the MS430502M chassis to be
managed from any system or PC in your network using network
management software. Consult the MS430502M chassis user manual
for information relating to the system set-up.